PERSONNEL SAFETY

Personnel
Safety Alarm

GBC2000-PSA / Kit: GBC2000-PSK

Designed to alert staff if a person is trapped within a walk-in coldroom or freezer. Fitting this unit to a coldroom ensures the installation complies with BS EN 378-1:2016 Annex D. High-integrity, fail-safe dual-channel technology with 10-hour battery backup that stays operational with multiple failures.

BATTERY BACKUP

10 Hours

INGRESS PROTECTION

IP65 Rated

SOUNDER OUTPUT

95 dB @ 30cm

TECHNOLOGY

Dual Watchdog

SUPPLY VOLTAGE

85 – 264 Vac

RELAY OUTPUTS

Alarm + Fault

KIT ORDER CODE
GBC2000-PSK
HOW IT WORKS

High-integrity fail-safe protection

Dual watchdog channel

Dual-channel processing provides a high-reliability alarm system that stays operational with multiple failures.

10-hour Ni-MH battery

A Ni-MH battery pack keeps the unit operational for up to 10 hours if the mains supply fails. We recommend replacing it at least every 3 years.

Monitored alarm relay

Monitored alarm relay output plus a separate fault relay output, with main relay faults detected by the system.

Integrated 95 dB sounder

Integrated 95 dB beacon/sounder, plus a remote external beacon/sounder with connection monitoring.

Self-checking, low maintenance

As a high-integrity self-checking system, it needs no significant routine maintenance beyond periodic battery replacement.

Full-system fault detection

Detects multiple system failures such as mains failure, battery backup failure, external beacon disconnected, main relay fault, processing fault and power fault.

Power status & alarm LEDs

Dedicated LEDs provide at-a-glance indication of power status and active alarm state directly on the unit.

COMPLETE SYSTEM

Everything in the kit

GBC2000-PSA

Main Control Unit

IP65
122×120×63 mm
85–264 Vac
Light Grey RAL7035
GBC2000-EB1 coldroom pushbutton fitted in GBC2000-PG1 stainless steel guard
GBC2000-EB1 / GBC2000-PG1

Coldroom Pushbutton & Guard

IP66
−40°C to +70°C
SS304 Guard
Illuminated
GBC2000-BS1 external beacon / sounder
GBC2000-BS1

External Beacon / Sounder

IP66
95 dB @ 30 cm
−20°C to +70°C
12 Vdc
GBC2000-BS2 beacon / sounder
GBC2000-BS2

Beacon / Sounder (Optional)

IP45 / IP66
9–30 Vdc
32 Tones
EN 54-3
TECHNICAL DATA

Full specifications

PARAMETER
VALUE
PHYSICAL
Model
GBC2000-PSA
Dimensions
122 mm W × 120 mm H × 63 mm D
Material
ABS, PC (UV stabilised) — Light Grey RAL7035
Ingress Protection
IP65 to EN 60529
Operating Temperature
0°C to +40°C
SUPPLY
Supply Voltage
85 – 264 Vac / 47 – 63 Hz
AC Current (typical at 230 V)
20 mA
Battery Backup
Ni-MH — up to 10 hours; replace every 3 years
INPUTS
Switched Input Voltage / Current
12 V dc / 10 mA
Maximum Cable Length
30 metres
OUTPUTS
Ext. Beacon Output
12 V dc / 130 mA max.
Maximum Cable Length (Beacon)
30 metres
ALARM RELAY OUTPUT
Nominal Switching Capacity
3 A @ 250 Vac / 3 A @ 30 Vdc (resistive)
FAULT RELAY OUTPUT
Nominal Switching Capacity (resistive)
2 A @ 250 Vac / 1 A @ 30 Vdc
Maximum Switching Power
500 VA / 30 W
Minimum Switching Capacity
100 mA @ 5 Vdc
PARAMETER
VALUE
PHYSICAL
Model
GBC2000-EB1
Pushbutton Dimensions
68 mm W × 68 mm H × 86 mm D
Guard Dimensions
110 mm W × 80 mm H × 96 mm D
Pushbutton Material
Polycarbonate — Grey RAL7035 / Yellow RAL1021
Guard Material
304 Grade Brushed Stainless Steel
Pushbutton
Illuminated
Ingress Protection
IP66 to EN 60529
Operating Temperature
−40°C to +70°C
SUPPLY
Supply Voltage / Current
Custom waveform 12 Vdc / 15 mA peak
PARAMETER
VALUE
GBC2000-BS1 — Physical
Model
GBC2000-BS1
Dimensions
68 mm W × 68 mm H × 60 mm D
Material
Polycarbonate — Grey RAL7035 / Yellow RAL1021
Ingress Protection
IP66 to EN 60529
Operating Temperature
−20°C to +70°C
Sound Pressure Level
95 dB @ 30 cm
GBC2000-BS1 — Supply
Supply Voltage / Current
12 Vdc / 25 mA peak
GBC2000-BS2 (Optional) — Physical
Model
GBC2000-BS2 (optional — not supplied with the kit)
Body Colour
Red or white
Ingress Protection
IP45 (standard base) / IP66 (deep base)
Operating Temperature
−15°C to +40°C (Xenon) / −20°C to +70°C (LED)
Beacon
Xenon or LED — 1 flash per second
Sounder
32 user-selectable tones; high, medium (−10 dB(A)) or low (−20 dB(A)) volume
Approvals
EN 54-3, LPCB approved
GBC2000-BS2 (Optional) — Supply
Operating Voltage
9 – 30 Vdc (24 Vdc, 20 – 28 Vdc to EN 54-3)
Flash Current
40 mA Xenon / 16 mA LED @ 24 Vdc; 90 mA Xenon / 12 mA LED @ 12 Vdc
Product Datasheet — GBC2000-PSA