TEMPERATURE MONITORING

Temperature
Monitoring (LAN)

GBSM-122-01 / GBSM-122-02 / GBSM-122-03NC

Monitor coldroom temperatures and send email alerts over your Local Area Network (LAN). Three standard variants — base model, battery backup, or battery backup with digital input/output relays.

IP Rating

IP55 Rated

Connectivity

LAN

Battery Backup

4 Hours

Sensors

Up to 2

Alerts

Email (SMTP)

Supply

90 – 264 Vac

ORDER CODES
GBSM-122-01 / GBSM-122-02 / GBSM-122-03NC
HOW IT WORKS

LAN-connected temperature monitoring

Email alarm alerts

Email alerts to 1 recipient using SMTP with authentication. All sensor variables can trigger an email alert, with deadband but no alarm delay.

Local alarm output

Relay outputs trigger a local beacon/sounder from the monitored temperature or humidity. Up to 2 sensor variables can be set to trigger the alarm relay.

Browser-based setup

Set up the panel from a web browser over your Local Area Network.

4-hour battery backup

GBSM-122-02 and GBSM-122-03NC include battery backup with a 4 hour power reserve.

Up to 2 sensors

Connect up to 2 temperature or temperature & humidity sensors (GBTST100 or GBTSH202).

Extra I/O on GBSM-122-03NC

Adds digital input/output relays, a volt-free alarm input for external devices such as plant equipment, and connections for a remote silence key-switch.

Free mobile app

App for Android® and Apple® devices for remote setup, monitoring and control.

SYSTEM COMPONENTS

Panel and sensors

GBSM-122

LAN Monitoring Panel

IP55 Rated
3 Variants
90–264 Vac
NTC temperature probe with coiled cable
GBTST100

Digital Temperature Sensor

−40°C to +85°C
1m Cable (max. 10m)
IP65
GBTSH202

Temperature & Humidity Sensor

20–80% RH
−10°C to +60°C
±0.4°C / ±3.0% RH
TECHNICAL DATA

Full specifications

PARAMETER
VALUE
PHYSICAL
Model Variants
GBSM-122-01 (no battery) / GBSM-122-02 (battery backup) / GBSM-122-03NC (battery backup + I/O)
Dimensions
230 mm W × 310 mm H × 130 mm D (-01, -02) / 310 mm W × 390 mm H × 130 mm D (-03NC)
Enclosure Material
Polycarbonate — Light Grey RAL7035
Ingress Protection
IP55 to EN 60529
Operating Temperature
0°C to +50°C
SUPPLY
Supply Voltage
90 – 264 Vac / 47 – 63 Hz
AC Current (typical at 230 V)
1.0 A
Battery Backup
4 hour power reserve (GBSM-122-02 and -03NC)
INPUTS
Sensors
Up to 2 — GBTST100 digital temperature or GBTSH202 temperature & humidity
NETWORK & ALERTS
Interface
Local Area Network (LAN)
Email Alerts
SMTP with authentication — 1 recipient
Setup
Web browser interface / free app for Android® and Apple®
ALARMS & I/O
Alarm Relay
Triggers local beacon/sounder — up to 2 sensor variables assignable
Alarm Input (-03NC)
Volt-free contact from an external device or system, e.g. plant equipment
Remote Silence (-03NC)
Connection for a remote silence key-switch
PARAMETER
VALUE
GBTST100 DIGITAL TEMPERATURE SENSOR
Sensor Head Dimensions
8 mm × 8 mm × 23 mm long
Cable
1 m silicone cable (extendable to 10 m max.)
Ingress Protection
IP65 to EN 60529
Supply Voltage
3 – 5.5 Vdc
Temperature Range
−40°C to +85°C
Accuracy (−10°C to +85°C)
±0.5°C
Accuracy (−40°C to +85°C)
±2.0°C
Resolution
12 bit / 0.0625°C
GBTSH202 TEMPERATURE & HUMIDITY SENSOR
Sensor Head Dimensions
16 mm × 10 mm × 45 mm long
Cable
1 m silicone cable (extendable to 10 m max.)
Ingress Protection
IP00 to EN 60529
Supply Voltage
4 – 5.5 Vdc
Temperature Range
−10°C to +60°C
Humidity Range
20% to 80% RH
Accuracy
±0.4°C / ±3.0% RH
Resolution
0.1°C / 0.1% RH
PARAMETER
VALUE
INPUTS / OUTPUTS (GBSM-122-03NC)
Switched Input Voltage / Current
12 V dc / 20 mA
Beacon Output Voltage / Current
12 V dc / 100 mA
Product Datasheet — GBSM-122